SIGNALSANALOGUE CURRENT / LOOP

4–20 mA Current Loop: Wiring, Scaling & Troubleshooting

A 4–20 mA loop represents a process value by regulating current in a series circuit. The normal measurement range runs from 4 mA at the lower range value to 20 mA at the upper range value, giving a 16 mA span and a live zero for basic fault discrimination.

Check the transmitter type, receiving input, polarity, available supply voltage, total series burden, cable resistance and configured measurement range.

QUICK CHECK

Before troubleshooting a 4–20 mA signal, verify whether the transmitter and PLC channel are wired as active or passive devices and calculate the available loop-voltage budget at maximum current.

01 · PRINCIPLE

How a 4–20 mA current loop works

The loop is a series circuit. A DC supply provides the available voltage, the transmitter regulates the loop current according to the measured variable, and the receiving input measures that current. Because the devices are in series, the instantaneous loop current is the same through each series element.

The receiver may measure current directly or convert it to voltage across an internal precision resistor. A 250 Ω shunt, for example, produces 1 V at 4 mA and 5 V at 20 mA. That is a common arrangement, but the actual input resistance must be taken from the PLC or instrument specification.

Flow transmitter, PID controller and control valve connected by 4–20 mA signals in a process-control loop
Example of 4–20 mA signals carrying a flow measurement, control setpoint and valve-position command in a process-control system.
Important: cable resistance does not directly create a proportional measurement error the way it can in a voltage signal. It does, however, consume loop voltage. If the transmitter runs out of compliance voltage, it can no longer maintain the commanded current.
02 · LIVE ZERO

Why the signal starts at 4 mA, not 0 mA

The 4 mA lower endpoint is a live zero. At the bottom of the configured measurement range, current is still flowing, which allows a two-wire transmitter to remain powered and helps distinguish a valid zero-percent process value from a dead or open loop.

4 mA means

The process variable is at the configured lower range value, provided the instrument is healthy and correctly ranged.

0 mA usually means

The loop is open, power is missing, wiring is disconnected, a fuse is open, or the transmitter is otherwise unable to drive the loop.

Do not treat every value below 4 mA or above 20 mA as the same fault. Smart transmitters can intentionally drive defined underrange, overrange or alarm currents, and the exact thresholds depend on the device configuration and the standard it follows.

03 · WIRING

Two-wire loop wiring and active/passive inputs

A two-wire transmitter uses the loop both for operating power and for the measurement signal. A common external-supply arrangement is:

  1. Power-supply positive to transmitter positive.
  2. Transmitter negative to the positive/current terminal of the receiving analogue input.
  3. Analogue-input return/common back to power-supply negative.

Some PLC and DCS current inputs provide loop power themselves. Others are passive measurement inputs and require an external supply. Vendors also use the words active, passive, source and sink differently, so the wiring diagram for the exact input card and transmitter takes priority over terminology.

Examples of 4–20 mA current-loop interfacing, showing source and sink capability, inline readout and controller-to-valve signalling
Examples of loop interfacing and powering.
Before energising: confirm polarity, whether the input supplies loop power, the permitted transmitter supply range, the input burden, and whether any isolator, indicator or barrier adds another series voltage drop.
04 · LOOP POWER

Loop voltage budget and maximum resistance

The supply must provide enough voltage for the transmitter plus every series voltage drop at the highest required loop current. If the available voltage is too low, the transmitter reaches its compliance limit and the current can clip below the correct value.

Vsupply ≥ Vtransmitter min + Imax × (Rinput + Rwire + Rother) + VmarginUse the transmitter manufacturer’s load curve when available; it is the authoritative limit.

Example: 24 V supply

Assume a 24 V supply, a transmitter that requires at least 10 V, a 250 Ω receiving input, 50 Ω total cable resistance and a 2 V design margin. At 20 mA, the receiving input drops 5 V and the cable drops 1 V. The loop therefore needs 10 + 5 + 1 + 2 = 18 V, leaving 6 V of additional headroom.

250 Ω INPUT20 mA × 250 Ω = 5.0 V
50 Ω WIRING20 mA × 50 Ω = 1.0 V
HEADROOM24 V − 18 V = 6.0 V

Rearranging the voltage-budget equation gives the maximum permitted external resistance:

Rmax = (Vsupply − Vtransmitter min − Vmargin) / Imax

With 24 V, 10 V minimum transmitter voltage, 2 V margin and 20 mA maximum current, the available external resistance is 600 Ω. That 600 Ω must cover the receiving input, cable and any other series burden.

Design current: 20 mA is the normal full-scale value. If the loop must remain compliant during a configured high alarm or another current above 20 mA, use that higher specified current when checking the voltage budget.
05 · SCALING

Scaling 4–20 mA into engineering units

For a linear transmitter, 4 mA corresponds to the lower range value (LRV) and 20 mA to the upper range value (URV). The usable measurement span is 16 mA.

PV = LRV + ((I − 4 mA) / 16 mA) × (URV − LRV)PV = process value. This assumes a conventional linear 4–20 mA mapping.
4 mA0%
8 mA25%
12 mA50%
16 mA75%
20 mA100%
Linear 4–20 mA mapping across the 16 mA measurement span.

Example: 0–10 bar pressure transmitter

At 12 mA, the signal is halfway through the 16 mA span. The corresponding process value is 5 bar. At 8 mA it is 2.5 bar; at 16 mA it is 7.5 bar.

Examples of linear 4 to 20 milliamp scaling into engineering units
CurrentPercent of span0–10 bar example
4 mA0%0 bar
8 mA25%2.5 bar
12 mA50%5.0 bar
16 mA75%7.5 bar
20 mA100%10.0 bar
06 · DIAGNOSTICS

NAMUR NE 43 fault and out-of-range currents

For devices configured to NAMUR NE 43, 4–20 mA remains the nominal measuring span. Values just outside it can indicate underrange or overrange rather than device failure: commonly used range limits are 3.8 mA and 20.5 mA, while failure alarm currents are driven to ≤ 3.6 mA or ≥ 21.0 mA.

≤ 3.6 mALow failure indication on NE 43-configured devices.
3.8 / 4–20 / 20.5 mAUnderrange limit · nominal measuring span · overrange limit.
≥ 21.0 mAHigh failure indication on NE 43-configured devices.

Currents from above 3.6 mA to 3.8 mA, and from above 20.5 mA to below 21.0 mA, lie between the nominal range limits and the failure-alarm thresholds. PLC thresholds should therefore match the transmitter documentation and configured alarm settings.

07 · TROUBLESHOOTING

Troubleshooting a 4–20 mA loop

Work from the electrical loop outward. First determine whether the problem is absence of loop power, inability to drive the required current, incorrect scaling, or a disagreement between the measured current and the PLC value.

  1. Verify loop power. Measure the DC supply and confirm that the transmitter sees enough terminal voltage while the loop is operating.
  2. Measure the actual current. A conventional multimeter must be inserted in series, which opens the loop during connection. A suitable mA process clamp can measure loop current without breaking the circuit.
  3. Compare field current with the PLC reading. If the measured mA value is correct but the PLC engineering value is wrong, check input configuration, raw scaling, LRV/URV and channel type.
  4. Check the voltage budget at high current. A loop that works near 4 mA but cannot reach 20 mA often has insufficient supply voltage or excessive series burden.
  5. Inspect wiring and terminals. Look for open conductors, reversed polarity, loose terminals, unintended grounds, barrier/isolator voltage drop and corrosion.
  6. Check transmitter diagnostics. If the current is intentionally below 4 mA or above 20 mA, determine whether the device is signalling underrange, overrange or an NE 43 alarm.
Troubleshooting checks for common 4 to 20 milliamp loop symptoms
SymptomLikely checks
0 mAPower supply, fuse, open circuit, disconnected return, failed transmitter.
Stable but wrong mASensor calibration, transmitter range, process condition, source simulation.
Correct mA, wrong PLC valueChannel configured for current, raw-count scaling, LRV/URV, input range.
Cannot reach 20 mASupply voltage, transmitter compliance, input burden, cable resistance, series devices.
Unstable currentLoose connections, supply instability, electrical interference, grounding/shielding practice, transmitter fault.
08 · SELECTION

Advantages and limitations of 4–20 mA

Advantages

  • Good immunity to induced voltage noise in industrial environments.
  • Long cable runs are practical when the loop voltage budget is adequate.
  • Live zero helps distinguish a valid low reading from a dead loop.
  • Two-wire transmitters can obtain operating power from the same loop.
  • Broad compatibility across transmitters, PLCs, DCS systems and indicators.

Limitations

  • Each conventional loop normally represents one process variable.
  • Every series device consumes part of the available voltage budget.
  • Analogue current alone does not carry rich device diagnostics.
  • An incorrect active/passive loop-power arrangement can prevent the loop from operating.
  • HART can add digital communication, but it has its own loop requirements.

For short, electrically quiet runs where both devices are designed for voltage signals, a 0–10 V interface can be simpler. For industrial field instrumentation, current loops are usually preferred when distance, noise immunity and live-zero diagnostics matter.