REFERENCEUNITS & CONVERSIONS

SI Units & Unit Conversions for Sensors & Measurement

The International System of Units (SI) provides a consistent basis for sensor specifications and measurement results. Convert only between units of the same physical quantity, keep prefixes and unit symbols case-sensitive, and distinguish simple scale-factor conversions from offset conversions such as °C to °F.

Pressure, temperature, flow, length, force and electrical signals are often reported in several unit systems. The conversion must preserve the physical quantity, reference condition and measurement basis—not only the numerical value.

Reference mass and digital weighing instrument used for measurement calibration
Units provide the reference attached to a numerical quantity value. Correct conversion changes the numerical representation without changing the physical quantity.
QUICK CHECK

Unit symbols are not abbreviations. Write 5 mm, 20 °C, 250 kPa and 4 mA with a space between the number and unit symbol; do not pluralise symbols or add a full stop unless normal punctuation requires one.

01 · SI FOUNDATION

The SI is built from seven base units and coherent derived units

The SI has seven base quantities and base units. Other SI units are formed from these through algebraic relations. For sensor engineering, the most frequently encountered derived units include the pascal for pressure, newton for force, joule for energy, watt for power, volt for electric potential, ohm for resistance and hertz for frequency.

Seven SI base units
Base quantitySI unitSymbolTypical sensor context
TimesecondsSampling, response time, pulse period
LengthmetremPosition, displacement, distance, level
MasskilogramkgMass, density, mass flow
Electric currentampereA4–20 mA loops and current measurement
Thermodynamic temperaturekelvinKTemperature and temperature compensation
Amount of substancemolemolGas and chemical measurement calculations
Luminous intensitycandelacdOptical and photometric measurement
Coherent units: when coherent SI units are combined according to the defining quantity equation, no extra numerical conversion factor is introduced. For example, 1 Pa = 1 N/m².
02 · SYMBOLS & PREFIXES

Prefix and unit symbols are case-sensitive

SI prefixes form decimal multiples and submultiples. In sensor work, the difference between uppercase and lowercase symbols is critical: m can mean metre when used as a unit or milli when used as a prefix, while M means mega. The prefix is attached directly to the unit symbol and only one prefix is used at a time.

Common SI prefixes in sensor engineering
PrefixSymbolFactorExample
gigaG10⁹GHz
megaM10⁶MPa, MΩ
kilok10³kPa, kΩ
millim10⁻³mm, mA, mV
microµ10⁻⁶µm, µA
nanon10⁻⁹nm, nF
picop10⁻¹²pF

Correct notation

  • 12.5 kPa
  • 4 mA
  • 100 µm
  • 25 °C
  • 293.15 K

Common notation errors

  • 12.5 KPa — wrong prefix case
  • 4 mA. (mid-sentence) — full stop incorrectly added to the unit symbol
  • 100 um — use µm where the character set permits
  • 25° C — space belongs before °C, not inside the symbol
  • 293.15 °K — kelvin uses K, not °K

The kilogram is a special naming case because the SI base unit already contains the prefix kilo. Decimal multiples and submultiples of mass are normally formed from the gram: 1 mg = 10⁻⁶ kg, 1 g = 10⁻³ kg and 1 Mg = 10³ kg. Forms such as “mkg” are not used.

03 · COMMON MEASUREMENT UNITS

Industrial sensor quantities often use SI units alongside accepted non-SI units

Sensor datasheets and control systems commonly mix SI and non-SI units. A conversion is valid only when the units represent the same physical quantity. Converting pressure to force, for example, requires an area as additional information; it is not a unit conversion alone.

Common units in industrial sensor measurement
QuantitySI unitOther common unitsImportant distinction
PressurePakPa, MPa, bar, mbar, psi, atm, TorrAbsolute, gauge and differential reference must be preserved
TemperatureK°C, °FTemperature values and temperature intervals convert differently
Volume flowm³/sm³/h, L/min, L/s, US gal/minGas reference conditions matter for standardised volume flow
Mass flowkg/skg/h, t/h, lb/hDo not convert directly to volume flow without density
Lengthmmm, µm, inch, footArea and volume require squared or cubed conversion factors
ForceNkN, lbfMass and force are different quantities
FrequencyHzkHz, rpmrpm is rotational rate; 1 Hz = 60 rpm only for one event per revolution

Other common derived quantities include acceleration in m/s², density in kg/m³, torque in N·m and electrical resistance in Ω. The unit expression matters: N·m is used for torque, while the joule is also dimensionally N·m but represents energy. Matching dimensions alone does not make two differently defined quantities interchangeable.

04 · CONVERSION METHOD

Most unit conversions are scale factors; some also require an offset

For units that share the same zero, conversion is usually multiplication by a constant factor. Pressure between Pa and bar and length between metres and inches are examples. Temperature scales such as Celsius and Fahrenheit use different zero points, so a simple factor is not sufficient for temperature values.

value in target unit = value in source unit × conversion factorThis multiplicative form applies only when the two units have compatible zero points and the factor is defined for the same physical quantity.
  1. Identify the quantity. Confirm that both units represent the same quantity: pressure to pressure, length to length, volume flow to volume flow.
  2. Preserve the reference. Gauge pressure must remain gauge pressure; absolute pressure must remain absolute pressure. Standard gas flow must retain its stated reference conditions.
  3. Apply the correct factor or equation. Use a traceable conversion factor and enough digits for the required measurement accuracy.
  4. Round at the end. Keep guard digits through intermediate calculations and round the final result to a precision justified by the source measurement.
Squared and cubed units: if 1 in = 25.4 mm exactly, then 1 in² = (25.4 mm)² = 645.16 mm² and 1 in³ = (25.4 mm)³ = 16 387.064 mm³. Do not apply the linear factor only once.

When a conversion factor is exact, the conversion itself does not introduce measurement uncertainty. Uncertainty still belongs to the measured value and any non-exact constants used in the measurement model. Using a rounded conversion factor can, however, add a small numerical error, so retain enough digits when accuracy matters.

05 · TEMPERATURE

Temperature values require offsets; temperature intervals do not

Kelvin and degree Celsius have the same unit size, but their zero points differ by exactly 273.15. Therefore a temperature value converts as K = °C + 273.15. Fahrenheit uses both a different zero and a different degree size, so °F = °C × 9/5 + 32.

K = °C + 273.15    |    °C = (°F − 32) × 5/9    |    °F = °C × 9/5 + 32For temperature differences, 1 K = 1 °C interval and 1 °F interval = 5/9 K. Do not add 273.15 when converting a temperature difference.
Temperature conversion examples
Condition°CK°F
Water freezing point at standard pressure0273.1532
Example process temperature20293.1568
Example process temperature100373.15212
Temperature interval10 °C interval10 K18 °F interval
06 · PRESSURE

Pressure conversion is simple only after the reference type is fixed

The pascal is the SI unit of pressure: 1 Pa = 1 N/m². Common industrial units convert by fixed scale factors, but the pressure reference—absolute, gauge or differential—must not be changed by the conversion. A reading of 2 bar(g) is not the same physical pressure as 2 bar(a).

Pressure conversion factors
Starting unitEquivalent in pascalsUseful relation
1 kPa1 000 Pa100 kPa = 1 bar
1 MPa1 000 000 Pa1 MPa = 10 bar
1 bar100 000 Pa1 bar = 100 kPa
1 psi≈ 6 894.757 Pa1 bar ≈ 14.5038 psi
1 atm101 325 Pa1 atm = 101.325 kPa
1 Torr≈ 133.322 Pa760 Torr = 1 atm
Pressure transmitter connected to a reference gauge and pressure calibration instrument
Pressure values can be reported in Pa, kPa, MPa, bar or psi, but unit conversion must preserve whether the measurement is absolute, gauge or differential.
Liquid-column units: units such as inH₂O and mmH₂O depend on conventional definitions or stated reference conditions. For precision work, use the exact definition specified by the instrument, standard or calibration certificate.
07 · FLOW

Liquid volume-flow conversion is straightforward; gas flow may depend on reference conditions

For an incompressible liquid, conversions among m³/s, m³/h, L/s and L/min are scale-factor conversions. Gas flow is different when the reported value is a standardised or normalised volume flow, because the numerical volume depends on the reference temperature, pressure and sometimes humidity or gas composition.

Common volume flow conversions
Starting valueEquivalentEquivalent
1 m³/s3 600 m³/h60 000 L/min
1 m³/h16.6667 L/min0.277778 L/s
1 L/min0.06 m³/h0.0166667 L/s
1 US gal/min3.785411784 L/min0.2271247 m³/h
Standard gas flow: abbreviations such as sccm, slm, Nm³/h and Sm³/h are not complete specifications unless the reference temperature and pressure are known. Two instruments can display the same nominal “standard” unit while using different reference conditions.
mass flow = volume flow × densityThis relation converts between mass flow and actual volume flow only when density corresponds to the same process state. For gases, density changes strongly with pressure, temperature and composition.

Do not treat standardised volume flow as actual pipe volume flow without converting through the applicable gas state. A mass-flow device can report kg/h independently of downstream display units, while a volumetric device may require pressure and temperature data before an equivalent mass flow can be calculated.

08 · SENSOR SIGNAL SCALING

Electrical signal scaling and engineering-unit conversion are separate steps

A transmitter converts a physical quantity to an electrical signal such as 4–20 mA or 0–10 V. The PLC, controller or DAQ then scales that signal back into an engineering quantity. If the desired display unit changes from bar to kPa, the engineering-unit conversion should be applied to the scaled physical value rather than changing the electrical meaning of 4 mA or 20 mA.

PV = LRV + (signal − signallow) × (URV − LRV) ÷ (signalhigh − signallow)For a 4–20 mA transmitter, signallow = 4 mA and signalhigh = 20 mA. LRV and URV must use the same engineering unit before the calculation.
Example 4 to 20 milliamp pressure scaling
Loop current0–10 bar scalingEquivalent 0–1000 kPa scaling
4 mA0 bar0 kPa
8 mA2.5 bar250 kPa
12 mA5 bar500 kPa
16 mA7.5 bar750 kPa
20 mA10 bar1 000 kPa

For non-linear sensors, conversion can also be embedded in the transfer relation. Thermocouple voltage, RTD resistance and differential-pressure flow are examples where the physical measurement model is not merely a change of display units.

09 · CONVERSION CHECKS

Most unit-conversion mistakes come from the quantity definition, not the arithmetic

  1. Write the quantity with every value. “250” is incomplete; “250 kPa(g)” carries both unit and pressure reference.
  2. Check prefix case. m, µ, k and M differ by factors of thousands or millions.
  3. Separate value from interval for temperature. A 10 °C rise is a 10 K interval, not a conversion to 283.15 K.
  4. Square or cube the conversion factor where required. Area and volume do not use a linear length factor.
  5. Preserve gas reference conditions. Standard or normal volume flow must retain the reference temperature and pressure.
  6. Do not confuse mass with force. Kilogram is a unit of mass; newton is a unit of force.
  7. Keep enough digits through the calculation. Premature rounding can create an avoidable error larger than the sensor resolution.
  8. Record the conversion in the measurement chain. PLC scaling, historian units and exported data should use the same quantity definition and unit metadata.
Comparison rule: convert competing sensor specifications to a common unit before comparing them, but keep the original reference conditions, uncertainty basis and percentage denominator. Equal-looking numbers can still describe different test conditions.